On load tap changer analyzer HYKC-2000

On load tap changer analyzer HYKC-2000 is a comprehensive measuring instrument for measuring and analyzing the electrical performance indicators of on-load tap-changers for power transformers and special transformers in power systems, which is mainly applied to test transient time, transition waveform, transition resistance, synchronization status of three phase.



Features
Technical Specification
Three phase constant current source charge, charge current3A/1A; 0.6A/0.2A
Maximum voltage of the port24V
Maximum range of transition resistance100Ω
Measuring range 1A:0.4Ω~20Ω 
0.2A:10Ω~100Ω
Record time of waveform300ms
Sample rate30k
Resolution of time0.1ms
Resolution of resistance0.1Ω
Accuracy of transition resistance±5% Reading±0.1Ω
Accuracy of transient time±0.5% Reading±0.2ms
Temperature-10-40℃  
Humidity<85%RH


Product Certificates

Calibration certificate of On load tap changer analyzer HYKC-2000 issued by Hubei Institute of Measurement and Testing Technology