CT PT Analyzer HYVA-405
HYVA-405 is used to measure all kinds of current transformer and voltage transformer. It can calculate the ratio errors and phase angle errors of current transformer and voltage transformer at rated burden and working burden in one time test. The tester can automatically evaluate the test results according to the selected standard to determine whether the transformer is qualified.
Tests for Current Transformer:
1)Ratio error and phase error test for all CTs
2)Excitation curve and knee point test for all CTs
3)Instrument factor FS test of measurement CTs
4)Accuracy limit factor ALF measurement of protection CTs
5)CT Winding resistance measurement
6)Short current factor Kssc and dimension factor Ktd test for transient protection CTs
7)CT polarity test
8)CT secondary burden test
9)CT nameplate deduce
10) Test multi taps CT with switch box
11) Test bush CT inside body of power transformer
Tests for Voltage Transformer:
1) Ratio error and phase error test of VT
2) Excitation curve test of VT
3) VT Secondary burden test
4) Winding resistance test of VT primary and secondary
5) VT and CVT ratio error test with 4KV voltage booster
6) VT induce voltage withstand test
General functions:
1) Making word report automatic
2) Auto comparison of test results and standard requirements. And then give conclusion pass or fail for sample CT
3) Tester can be operated by laptop through Ethernet port
4) PC application support bulk report making
1) Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, IEC60044-61869, GB-1207, GB-1208, GB-16849, C57.13
2) Power supply: AC220V±10%, 50/60Hz±10%
3) Voltage output: 0.1~160V AC(AC 0-4KV with external voltage booster)
4) Current output: 0.001~5A(RMS), Peak value 15A
5) Power output: 500VA
6) Maximum knee voltage measurement: 45KV.
7) Ratio error of CT: Typical <0.02%, Assured <0.1%, Resolution <0.01%
8) Make evaluation for test results according to selected standards
9) Make word report for all test results
10) Bulk report application could make more than 1000 test records in once a time
11) Measure the ratio errors and phase angle errors at rated burden and working burden in one time.
12) Compare excitation curves with saved excitation curves in the same window
13) Memory capacity: >30000 groups test results
14) Working condition: temperature: -10℃~50℃, humidty: ≤90%
15) Size: 485mm×356mm×183mm, weight: <15kg
Range | Error | Resolution | |
Current measurement | 0~10A (automatically change | <±0.1%+0.01%FS | / |
Voltage measurement | 0~200V (automatically change | <±0.1%+0.01%FS | / |
Turns ratio measurement | 1~2000 | <0.05% | / |
2000~5000 | <0.1% | / | |
5000~35000 | <0.2% | / | |
Phase measurement | / | <2min | Resolution: 0.01min |
Winding resistance measurement | 0~10kΩ (automatically change | <0.2%RDG+0.02%FS | Maximum resolution: 0.1mΩ |
Temperature measurement | -50~100 Celsius degree | <3 Celsius degree | / |
CT Secondary burden | 0~160ohm (automatically change range in 2ohm/20ohm/160ohm) | <0.2%RDG+0.02%FS | Maximum resolution: 0.001ohm |
PT Secondary burden | 0~80kohm (automatically change range | <0.2%RDG+0.02%FS | Maximum resolution: 0.1ohm |
PT Secondary admittance test | 0-100mS | <0.2%RDG+0.02%FS | Maximum resolution: 0.1ohm |
PT ratio measurement | 1~2000 | <0.1% | / |
2000~10000 | <0.2% | / | |
10000~35000 | <0.5% | / | |
1-2200 (With 4KV voltage booster) | <0.05% | / | |
VT ratio error measurement | / | <30min (phase error) | Resolution: 0.1min |
VT excitation mode ratio error measurement | / | <0.1% (ratio error ) <3min (phase error) | / |
CVT ratio measurement error | 1-2200 | < 0.05% | / |
-